Inverter clipping and the DC:AC ratio
Last updated .
Inverter clipping is the output an inverter cannot pass when the array's DC power rises above the inverter's AC rating, so the excess is lost at the peak. An array is commonly oversized against its inverter because it reaches peak power for only a few hours a year, and the extra panels add more yield in dull and off-peak light than the clipping at midday costs.
Inverter clipping is the solar energy an inverter cannot pass to the building or the grid, because the array's direct-current output has risen above the inverter's alternating-current rating, so the surplus is held back at the panels. The DC-to-AC ratio, also called the inverter loading ratio, is the array's rated DC capacity divided by the inverter's rated AC capacity, and any figure above 1.0 means the array can at times produce more than the inverter will pass. Building an array larger than the inverter it feeds is ordinary practice: the default DC-to-AC ratio in NREL's PVWatts Version 5 model is 1.1, the array built 10 per cent larger than the inverter it feeds. Why that oversizing usually shortens the payback is the subject of this guide.
What the DC:AC ratio is
The ratio sets the array's rated power against the inverter's. The array's figure is its nameplate DC capacity, the sum of its panel ratings measured under standard test conditions of 1,000 watts per square metre of irradiance and a cell temperature of 25°C, the conditions used for IEC 61215 type approval. The inverter's figure is its rated AC output, the most power it will deliver to the building or the grid whatever the panels behind it are doing. A ratio of 1.0 pairs an array with an inverter of exactly its nameplate size; a ratio above 1.0 gives the inverter less headroom than the array's peak, which is where clipping becomes possible.
The reason an array is built larger than its inverter is that the panels only reach their nameplate figure in a narrow band of conditions. The extra direct-current capacity offsets the slow ageing of the modules and lifts output in the weak light of the winter months, which is why a ratio above one is treated as standard practice.
Why the array rarely reaches its nameplate
Nameplate power assumes full sun on cool panels, and a real roof meets that for only a few hours a year. Most daylight is weaker than the 1,000 watts per square metre the panels are rated against, so for the morning, the evening, the overcast days and the whole of winter the array produces well under its rating and the inverter passes everything it makes. High cell temperature lowers the peak further on the brightest days, the very days clipping would otherwise cost the most. Silicon cells lose between 0.4 and 0.5 per cent of their output for every degree Celsius above their 25°C rating, so a panel at high temperature in July delivers less than its label suggests at the moment the sun is strongest. The hours when the array could genuinely exceed the inverter are therefore few, which is what makes a modest amount of clipping a price worth paying for the extra yield the larger array brings in across every other hour.
A worked example
Take an 11 kilowatt DC array wired to a 10 kilowatt AC inverter. The DC-to-AC ratio here is 1.1, the 11 kilowatts of panels divided by the 10 kilowatt inverter. At the rare moments the array delivers its full output against the inverter's 10 kilowatt limit, 1 kilowatt cannot be exported and is clipped. For most of the year the array sits well below its rating, so the inverter passes everything the panels make and nothing is lost.
What decides the payback is how much energy that clipped kilowatt adds up to across the year, and the total is small. The array reaches the inverter's limit for only a few hours near midday in high summer, and only the slice above 10 kilowatts is given up, so the energy lost across the year is a small share of the array's output. The clipping stays in the low single digits of annual generation at the usual commercial ratios, and the 1.1 ratio of this example is the standard commercial starting point. The extra panels that cause the clipping add output in every dull and off-peak hour the inverter had headroom to spare, so across the year they add more output than the clipped peak gives up. Whether the trade is worth making is an arithmetic question about how those two quantities compare over a year on the specific site.
How the ratio moves the payback
The DC-to-AC ratio changes the yield, and through the yield the payback. A higher ratio puts more panels behind the same inverter and the same grid connection, so the array generates more in the weak light that fills most of the year, lifting the self-consumption that drives the return on a commercial system. The cost is the growing slice of the summer peak lost to clipping, and the extra panels bought per kilowatt that are only ever used below their rating. Past a certain ratio the clipped energy outweighs the yield the next panels add, and the payback starts to lengthen again. The best ratio for a roof is the one that sits at the turn of that curve, found by modelling the array against the site's own half-hourly demand.
The site's connection limit changes which ratio is right. On a site whose export is limited or whose import capacity caps what the connection will carry, the peak the array could produce was going to be lost to that cap whatever the inverter did, so a higher DC-to-AC ratio can suit the site well: the extra DC fills the parts of the day that sit under the cap, and the peak it cannot export was never worth anything on that connection. The same ratio that wastes output on an unconstrained site can be the right one behind a constrained connection, which is why the decision belongs in the feasibility model next to the battery sizing and the payback.
A ratio chosen too high also shows up later as what can look like underperformance: an array that clips hard every summer reads below the yield its panels imply, when the cause is the chosen array size and the panels are working correctly. Reading the performance ratio correctly means knowing how much of a shortfall is clipping the design accepted and how much is a genuine loss.
How Lupa helps
Lupa models a solar array against a site's own half-hourly demand and its connection limit, so the DC-to-AC ratio follows from what the site will actually do with the energy. The platform shows the yield, the self-consumption and the clipping a given ratio produces, and the payback each one lands on, so an analyst can see where the next panels no longer shorten the payback and set the array's size against the connection the site really has.
Common questions
- What is inverter clipping?
- Inverter clipping is the solar output an inverter cannot pass through, because the panels are producing more direct-current power at that moment than the inverter is rated to convert to alternating current. The inverter holds its output at its rated ceiling and the surplus is left at the panels. It happens only in the brightest conditions, when the array is near its full rating, so on most sites it comes to a small share of the year's generation.
- What DC-to-AC ratio should a commercial array use?
- Commercial arrays are usually built at a DC-to-AC ratio between about 1.1 and 1.3, and the default DC-to-AC ratio in NREL's PVWatts Version 5 model is 1.1, the array a tenth larger than the inverter. A UK roof receives weaker and more diffuse sunlight than much of the United States, so it reaches the inverter's limit less often, and the upper end of that range tends to suit it. At these ratios the energy given up to clipping across a year is small, in the low single digits of the array's output, because the array only touches its inverter's limit for a few hours near midday in high summer. The right figure for a given roof comes from modelling the array against the site's own demand and connection limit. A higher ratio adds yield in dull and off-peak light, and it loses more of the midday peak to clipping. On a site whose export or import capacity already caps the peak, a higher ratio can suit it well, because that peak was going to be lost to the cap whatever the inverter did.
- Does clipping mean the array is the wrong size?
- Clipping by itself is not a sign of the wrong size. A small amount of clipping at the height of summer is the expected result of sizing an array a little larger than its inverter, and it is accepted because the extra panels add more output across the rest of the year than the clipped peak gives up. Clipping only points to a sizing problem when it is large enough that the wasted peak energy outweighs the yield the extra DC capacity brings in, which is a question of where the payback lands.